Power conversion system (PCS)
A power conversion system (PCS) is the bidirectional inverter in a battery storage system. It converts grid AC to DC to charge the battery and DC back to AC to discharge it, in the direction and quantity it is told to.
Key facts
- •A good commercial PCS is about 97–98.5 per cent efficient each way near rated load
- •Two passes therefore cost about three to five per cent, and more at light load
- •It responds within microseconds to milliseconds
- •It takes active and reactive power setpoints from the energy management system, clipped to what the BMS allows
- •Rated output in kVA limits active and reactive power combined
How it works
The PCS synchronises with the grid and keeps operating through voltage and frequency disturbances as the connection rules require. It has its own fast protection, but it has no view on whether discharging now is commercially sensible. That decision comes from the energy management system.
A large plant may use one central unit or many smaller string units. Central designs concentrate a failure into one unit; string designs spread it across several, at the cost of more units to maintain.
Worked examples
The smaller limit governs. A 1,000 kWh battery capable of 1C could deliver 1,000 kW, but with a 500 kW PCS the system delivers 500 kW at most, or 0.5C, for about two hours.
Efficiency compounds. At 98 per cent each way, 0.98 × 0.98 is about 96 per cent, so 4 per cent of the energy passing through is lost as heat that must also be removed.
Reactive power takes up capacity. Apparent power is the square root of (kW² + kVAr²). Delivering 500 kW and 300 kVAr together requires the square root of 340,000, or about 583 kVA, so a 500 kVA unit could not do both at once.
Why it matters to a buyer in India
Heat matters here. Many converters reduce their output above a stated ambient temperature, so a rating at a mild reference temperature may not apply in a hot enclosure in May. Part-load behaviour matters too: a unit running at a tenth of its rating is well away from its best efficiency, which affects a site where the battery often runs lightly.
Grid connection requirements vary by voltage level and location, so confirm them with your DISCOM before fixing a design.
- •Continuous kW and kVA rating at your site’s highest ambient temperature
- •The full efficiency curve, not only its peak
- •Compliance with applicable connection requirements
- •Who integrates the PCS with the BMS and the energy management system
Frequently asked questions
Is a PCS the same as an inverter?+
Broadly yes. A PCS is an inverter designed for storage, moving power in both directions and following external setpoints. Many solar inverters only convert DC to AC and cannot charge a battery from the grid, so the terms are not interchangeable in a specification.
Should a PCS be sized larger than the load it must serve?+
It should cover the required kVA at the worst site temperature, with some margin, including any reactive power it must supply. Heavy oversizing costs money and can mean more time at light load, where efficiency falls. Check the requirement against interval load data.
Read more
- BMS, PCS, EMS and SCADA: The Control Stack Inside a Battery Storage System Explainer
- Round-Trip Efficiency: Where the Energy Goes in a Battery Storage System Explainer
- Europe’s Storage Industry Asks for Tougher Cyber Checks on the Battery’s Control Layer News
- Inside the Fence: What a Battery Plant Is Made Of Besides Batteries Grid storage
- AC-Coupled vs DC-Coupled Solar-Plus-Storage: Which Architecture Fits Your Site C&I storage
- Grid-Forming vs Grid-Following Inverters: What Batteries Do for a Weak Grid Grid storage
Related terms
Is storage right for your site?
Send us a month of electricity bills and your load profile, and we will tell you what a battery would save — including when it would not pay.